6.0 DGA INTERPRETATION BASED ON IEEE 57.104 -2019
The DGA status is only one input to the process of determining a transformer’s condition.There is no direct and infallible method using DGA to obtain an exact evaluation of a transformer’s condition. There are several reasons why the DGA status can be very different from the transformer’s true condition, some of which are as follows:
a. There are several possible causes of the presence of gas in a transformer. Some of those are related to fault conditions (e.g., arcing, overheating, PD), others are related to more benign conditions (e.g., stray gassing, contamination, previous fault now inactive, and mild core overheating).
b. Some pre-failure conditions simply do not generate gas. (e.g., mechanical or insulating system weakness).
c. Some normal conditions do generate gases. (e.g., normal aging, and insulating liquid oxidation).
d. The DGA data used to develop this procedure and norms came from in-service transformers for which their condition information (faulty or not) at the time of the DGA was unavailable. Therefore, there was no possibility to directly correlate one with the other, only to evaluate the DGA results distribution assuming most of the data came from healthy transformers.
This guide clearly mentions that “ the methodology presented here will classify the DGA results, not the transformer condition. Users should not equate “DGA status” to “transformer condition.” It could be presumed that one is possibly related to the other, but there can be no guarantee in this respect. Transformers could fail without any prior gas generation, while others could be operating with high levels of gases.” Further this guide classifies DGA results into 3 groups as follows:
• DGA Status 1: Low gas levels and no indication of gassing. (Unexceptional DGA)
• DGA Status 2: Intermediate gas levels and/or possible gassing. (Possibly suspicious DGA)
• DGA Status 3: High gas levels and/or probable active gassing. (Probably suspicious DGA)
After data quality and confirmation issues have been addressed, interpretation of the DGA data can be undertaken. Prior DGA results should be used for characterization of increments and rates. If abnormal DGA results are found, any available supplementary information, such as test and maintenance records, load data, environmental conditions, etc., should be consulted for possible clues as to the origin and nature of the abnormalities. Comparison of DGA data from sister units, i.e., transformers built to similar specifications, is useful for spotting unusual results and for revealing common patterns, which may provide a better understanding of the data. Figure 8 is a flow chart that provides a suggested process to review the DGA results.
The following procedure explains the Figure 8 flowchart :
1. Compute the O2/N2 ratio. Compute the absolute variation [delta μL/L (ppm)] for each gas from the previous routine sample.
2. Update multipoint rate values using the last 3 to 6 data points over the last 4 to 24 months period, if available. If more than 6 data points are available, use the six most recent data points, not exceeding two years, to compute the rates.
3. If age is known, compare all gas values to the applicable column of Table 7, according to the O2/N2 ratio and age. If age is unknown, use the values in the column “Unknown” (under “Transformer age year header) of the applicable table. If the O2/N2 ratio is not available, the O2/N2 ratio >0.2 section should be used.
4. If all gas levels are below the applicable values in Table 7, compare the delta values to the applicable sections of Table 9. Compare rate values to the applicable sections of Table 10, if available.
5. If all gas delta values are below the applicable section of Table 7, and all rates values are below the applicable section of Table 10 (if available), then a DGA status of 1 is indicated. Continue routine sampling as per company policy.
6. If any delta is greater than the value in the applicable sections of Table 7, or any calculated generation rate is greater than the applicable sections of Table 10, perform a confirmation DGA within a month .
7. Compute the absolute variation (delta) between the reference sample and the confirmation sample. Compute rates with the confirmation sample replacing the previous value. If the confirmation sample does not indicate an increase from the previous sample (i.e., all gas variations delta are below the applicable section of Table 9 and all rates.below the applicable section of Table 10 norms), and all gas level values are also still below the applicable section of Table 7, DGA status is 1. Continue routine sampling per the company policy
8. If the second sample confirms an increase (Delta) has occurred but all gas level values are below the applicable section of Table
7 and all multi-point rates are below the applicable section of Table 10 values, then a DGA status of 2 is indicated.
9. If any one gas level is between the values in the applicable sections of Table 7 and Table
8 with no gas levels above the applicable sections of Table 8, and all multi-point rates are below the applicable section of Table 10, then a DGA status of 2 is indicated.
10. If only 1 sample per year is taken, there will not be enough samples to calculate the multipoint gas generation rates for comparison to Table 10, so only Table 9 would be used in such cases. If Table 9 values are exceeded, a confirmation sample is required, which will allow the computation of the rates (e.g., 3 samples in 2 years).
11. If any one gas level is above the applicable section of Table 8, or if any rate is above the applicable section of Table 10, a DGA status of 3 is indicated.
12. For DGA in status 3, gas evolution should be monitored for a significant period of time. If during that period of time there is no significant positive rate observed, then a lower DGA status could be considered, after consultation with a DGA expert.
13. For extremely high concentrations, deltas, or rates, consult a DGA expert.
It is also recognized that all faults are not of the same concern, so the type of fault should also be considered, not just the gas levels or the gas evolution. As DGA interpretation is still more of an art than a science, the consultation of a transformer expert with DGA interpretation experience is strongly encouraged.
6.1 ADDITIONAL SUB-TYPES OF FAULTS
The additional sub-types of faults indicated in this guide are:
a. Stray gassing of mineral oil (S) at temperatures < 200 °C (in mineral oil only), because of the chemical instability of mineral oils produced by some modern refining techniques. It could also occur due to incompatibility between materials (e.g., such as some metal pasivators).
b. Overheating (O) of paper or mineral oil < 250 °C (therefore without carbonization of paper and loss of its electrical insulating properties).
c. Possible carbonization of paper (C).
d. Thermal faults T3 in mineral oil only (no paper involved) (T3-H) .
e. Catalytic reactions (R) between water and galvanized steel in oil sampling valves of transformers or with tank stell (rust) (R faults are very rare)
6.2 DUVAL TRIANGLES 4 AND 5 METHODS
Duval Triangles 4 and 5 are built and used in the same manner but use different gases and zones. Duval Triangle 4 uses H2, CH4 and C2H6 and Duval Triangle 5 uses CH4, C2H4 and C2H6.Duval Triangles 4 and 5 can be utilized to obtain more information about sub-types of thermal faults. When low energy or low temperature faults are identified using the Duval Triangle 1 (PD, T1 or T2), more information can be obtained with Duval Triangle 4. Numerical values for fault zone boundaries of Duval Triangle 4 method are the following, expressed in %H2, %CH4 and %C2H6. Numerical values for fault zone boundaries of Duval Triangle 5 method are the following, expressed in %CH4, %C2H4 and %C2H6
The Triangle 5 method allows a user to distinguish between high temperature faults T3/T2 in mineral oil only, of lesser concern in transformers, and potentially more dangerous faults C involving possible carbonization of paper.
Note that:
a. Triangles 4 and 5 should never be used for faults identified first with Triangle 1 as electrical faults D1 or D2.
b. Triangle 4 should be used only in case of faults identified first as faults PD, T1 or T2 in Triangle 1.
c. Triangle 5 should be used only in case of faults identified first as faults T2 or T3 in Triangle 1.
d. DGA points occurring in zones C indicate a possibility of carbonization of paper, not a 100% certainty, and further investigations with carbon oxides and furans should be undertaken.
e. The procedure for calculating and displaying DGA points in Duval Triangles 4 and 5 is the same as for Triangle 1.
6.4 Duval Pentagon 2 Method The Pentagon 2 method allows for detection of the 3 basic types of electrical faults (PD, D1 and D2) as in Duval Pentagon 1, and to further distinguish between the 4 additional sub-types of thermal faults of S, O, C and T3 in mineral oil only. In Duval Pentagon 2, faults T3 in mineral oil only are indicated as T3-H, where H is for “Huile” or “oil” in French. NOTE—DGA points occurring in zone C indicate a possibility of carbonization of paper, not a 100% certainty, and further investigations with carbon oxides and furans should be undertaken. If thermal faults (T1, T2, and T3) have been identified with Duval Pentagon 1, more information an be obtained on these faults with Duval Pentagon 2, as in the case of Duval Triangles 4 and 5. The Duval Pentagon 1 & 2 method is illustrated in
6.5 Mixtures of faults
Duval Triangles 1, 4, 5 and Pentagons 1, 2 methods, as well as all other diagnosis methods (Key Gas, Rogers Ratios, Doernenburg Ratios), were initially developed for detecting single faults only. However, multiple faults (mixtures of faults) often occur rather than single faults and may be more difficult to identify with certainty. For instance, actual mixtures of faults T3+D1 may sometimes appear in terms of gas formation as faults D2 in Triangle 1, Pentagon 1, and other diagnosis methods (Rogers Ratios, etc.), while actual mixtures of faults T3 in mineral oil (T3-H) and O may appear as faults C in Triangle 5 and Pentagon 2. Mixtures of faults may be suspected when fault identifications provided by Duval Triangles 1, 4, and 5 and Pentagons 1 and 2 for the same DGA results are different. This is because each graphical representation is more sensitive to some gases and some faults than to others. For example, Triangle 4 and the Pentagons are more sensitive to H2 and faults S and PD, while Triangle 1 and Triangle 5 are more sensitive to C2H4 and faults T3. If the position of the DGA point changes with time in the Triangles and the Pentagons, this indicates that a new fault has formed over the old one or another source of gas formation (a different type of fault has become active) exists. To get a better identification of this new fault, gas concentrations from the previous DGA results may be subtracted from the most recent ones. The subtracted (delta) values will thus be due only to the new fault. If delta values are negative for some gases, this means that no additional amounts (zero μL/L) of these gases have been formed because of the new fault since the previous sample, and that some of those gases previously formed have started to escape from the transformer. When identifying the new fault, negative delta values should, therefore, be replaced by zero μL/L. The possible presence of multiple faults may be useful information during the inspection of transformers.
6.6 When to use the Duval Pentagons and Triangles
If interest is only in the six basic types of faults, the display of DGA points would be done using the Pentagon 1 or Triangle 1. If there is also an interest in the additional subtypes of faults as discussed Pentagon 2 and Triangles 4 or 5 should be used. When detection of mixtures of faults is desired, the diagnosis provided by the pentagons and the triangles can be compared. If they do not agree, this may be an indication of multiple faults. Use subtracted (delta) values as discussed above to further identify these multiple faults.
7.0 CONCLUSION
Dissolved gas analysis (DGA) is the identification, measurement, and interpretation of the gases dissolved in the insulating liquid. Whenever a transformer undergoes abnormal thermal and electrical stresses, certain gases are produced due to the decomposition of the transformer oil. The DGA diagnostic tools that have been discussed are considered to be the main interpretation methods used for fault diagnosis of power transformers. This includes the Key Gas, Dornenburg Ratio, Rogers Ratio, IEC Basic Gas Ratio, Duval Triangle, and key gases methods. The majority of these methods are ratio-based, meaning they use a subset of the ratios below to diagnose a fault type based on the fit of each ratio result to a specific range of values:
• Ratio 1 (R1) = CH4/H2
• Ratio 2 (R2) = C2H2/C2H4
• Ratio 3 (R3) = C2H2/CH4
• Ratio 4 (R4) = C2H6/C2H2
• Ratio 5 (R5) = C2H4/C2H6
It is important to remember that when using ratio-based diagnostic tools, minimum gas levels are required as defined in the guides, for the ratio analysis to be considered valid. The other methods based on IEEE C57.104.2019 have been discussed which are quite different from previous version. If interest is only in the six basic types of faults, the display of DGA points would be done using the Pentagon 1 or Triangle 1.If there is also an interest in the additional sub-types of faults as discussed Pentagon 2 and Triangles 4 or 5 should be used.
The key objective in DGA of fault gases is to correctly diagnose the fault that is potentially generated. Some diagnostic tools have the ability to perform better than others, so it’s important to review the most recent information when incorporating them into DGA procedures.
"AUTHOR- Dr. RAJESH KUMAR ARORA obtained the B. Tech. & Master of Engineering (ME) degrees in Electrical Engineering from Delhi College of Engineering, University of Delhi, India in 1999 and 2003 respectively. He completed his PhD in grounding system design from UPES, Dehradun. He is also certified Energy Manager and Auditor and has worked in 400kV and 220kV Substation for more than 14 years in Delhi Transco Limited (DTL). He has also worked as Deputy Director (Transmission and Distribution) in Delhi Electricity Regulatory Commission (DERC) for 03 years and 06 months. He has also given his contribution in the OS department of DTL for more than 2 years and rendered his services in the SLDC of Delhi Transco Limited (DTL) also. Presently he is working in D&E (Design and Engineering) department of DTL. His research interests include high voltage technology, grounding system, protection system, computer application and power distribution automation."
leave your comment